Pollution Degree and Electrical Enclosure Design

The air shouldn’t have dust, acid, salt, corrosive, or explosive gases. Unless stated otherwise, equipment works in pollution level 2 environments. If we use a higher design, we must note this in the documents.

We must protect electrical equipment from solids and liquids. Use Table 2.2.6 to decide water protection levels; other liquids need extra protection. If the installation site has pollutants (like dust, acid, corrosive gas, salt), suppliers and users may need a special agreement.

Table 2.2.6

Second NumberCodeProtection LevelSimple Explanation
0IPX0No protectionNo special protection
1IPX1Stops dripsVertical drips won’t cause harm
2IPX2Stops dripsIf the appliance tilts up to 15° from normal, vertical drips won’t cause harm
3IPX3Stops spraysSprays within 60° of the horizontal won’t cause harm
4IPX4Stops splashesSplashes from any direction won’t cause harm
5IPX5Stops jetsWater sprayed from a nozzle (any direction) won’t cause harm
6IPX6Stops wavesStrong waves or heavy sprays won’t let in enough water to cause harm
7IPX7Stops harm from being immersedIf the appliance is in water at a set pressure for a set time, not enough water gets in to cause harm
8IPX8Stops harm from divingIf the appliance dives for a long time at a set pressure, no water gets in

Notes:

  1. The “Simple Explanation” here is just a summary, not an official rule for protection.
  2. The “Explanation” tells us how the second number protects against water.

If a cabinet meets a level, it also meets all lower levels. We don’t need to test lower levels unless we’re unsure.

What Pollution Degree Describes

Pollution degree is an input used in insulation coordination under applicable standards. It reflects environmental contamination around electrical insulation, not a general cleanliness rating for the cabinet exterior.

Assess the Microenvironment

The relevant condition may be inside the enclosure rather than the room. Dust, humidity, condensation and conductive contamination can change the microenvironment.

Enclosure Design Measures

Sealing, ventilation, heaters, filters and cooling can influence internal conditions. Openings and maintenance practices must be considered with the complete system.

Coordinate With Clearances and Creepage

The electrical designer determines insulation distances from voltage, materials, pollution conditions and the applicable standard. The enclosure manufacturer needs the resulting layout and interface requirements.

Do Not Substitute IP for Pollution Degree

IP ratings and pollution degree address different questions. Neither should be inferred from the other without the relevant design and evidence.

Review cabinet safety and bonding and protection design. Send environmental and electrical requirements through the contact page.

Record the Design Assumptions

The specification should name the applicable standard, expected microenvironment and measures used to control contamination. Any change to ventilation, heating or installation conditions should be reviewed by the electrical designer.

Newsletter

Subscribe to our channel to learn more about electrical enclosures

Get A Quick Quote
Related products
How Can We Help? Contact Us Today!
Scroll to Top

schedule a chat

Fill out the form below, and we will be in touch shortly.
Contact Information
send us a message
Fill out the form below, and we will be in touch shortly.
CONTACT INFORMATION